CosΦ1为补偿前的功率因数;CosΦ2为补偿后的功率因数。K代表总电流与无功功率千乏值的比例系数。
Q=I总 х K
|
CosΦ2 K CosΦ1 |
0.90 |
0.95 |
0.98 |
1.00 |
|
0.30 |
0.565 |
0.598 |
0.624 |
0.667 |
|
0.35 |
0.537 |
0.575 |
0.605 |
0.655 |
|
0.40 |
0.506 |
0.549 |
0.584 |
0.641 |
|
0.45 |
0.473 |
0.522 |
0.561 |
0.625 |
|
0.50 |
0.437 |
0.491 |
0.535 |
0.606 |
|
0.55 |
0.398 |
0.458 |
0.505 |
0.584 |
|
0.60 |
0.357 |
0.422 |
0.475 |
0.560 |
|
0.65 |
0.311 |
0.382 |
0.439 |
0.531 |
|
0.70 |
0.263 |
0.339 |
0.40 |
0.50 |
|
0.75 |
0.210 |
0.290 |
0.357 |
0.463 |
|
0.80 |
0.149 |
0.236 |
0.307 |
0.420 |
|
0.85 |
0.08 |
0.173 |
0.247 |
0.368 |
|
0.90 |
|
0.10 |
0.177 |
0.305 |