●您所在的位置:首页 >> 电能质量 >> powerquality >> 正文

Power Factor Improvement


作者: 来源: 时间:07-12-20 加入收藏加入收藏夹
关键字:Power Factor Improvement  capacitor

When using power factor correction capacitors, the total KVAR on the load side of the motor controller should not exceed the value required to raise the no-load power factor to unity.Over correctiveness of this value may cause high transient voltages, currents, and torques that can increase safety hazards to personnel and possibly damage motor driven equipment.

 

Never connect power factor correction capictors at motor terminals on elecvator motors, plugging or jogging applications, multi-speed motors or open transition, wye-delta, auto-transformer starting and some part-winding start motors.

If possible, capacitors should be located at position 2 (see diagram). This does not change the current flowing through motor overload protectors. Connection of capacitors at position 3 requires a change of overload protectors. Capacitors should be located at position 1 for applications listed in paragraph 2 above. Be sure bus power factor is not increased above 95% under all loading conditions to avoid over excitation.

Diagram

Original
Power
Factor
Percent
Desired Power Factor Percent
100% 95% 90% 85% 80%
60% 1.333 1.004 0.849 0.713 0.583
62% 1.266 0.937 0.782 0.646 0.516
64% 1.201 0.872 0.717 0.581 0.451
66% 1.138 0.809 0.654 0.518 0.388
68% 1.078 0.749 0.594 0.458 0.328
70% 1.020 0.691 0.536 0.400 0.270
72% 0.964 0.635 0.480 0.344 0.214
74% 0.909 0.580 0.425 0.289 0.159
76% 0.855 0.526 0.371 0.235 0.105
78% 0.802 0.473 0.318 0.182 0.052
79% 0.776 0.447 0.292 0.156 0.026
80% 0.750 0.421 0.266 0.130
81% 0.724 0.395 0.240 0.104
82% 0.698 0.369 0.214 0.078
83% 0.672 0.343 0.188 0.052
84% 0.646 0.317 0.162 0.206
85% 0.620 0.291 0.136
86% 0.593 0.264 0.109
87% 0.567 0.238 0.083
89% 0.512 0.183 0.028
90% 0.484 0.155
91% 0.456 0.127
92% 0.426 0.097
93% 0.395 0.066
94% 0.363 0.034
95% 0.329 Assume Total plant load is 100 KW at 60% power factor. Capacitor KVAR rating necessary to improve power factor to 80% is found by multiplying KW (100) by the multiplier in table (0.583) which gives KVAR (58.3), nearest standard rating (60 KVAR) should be used.
96% 0.292
97% 0.251
99% 0.143

8

8

●相关新闻

无相关新闻
©2005-2006 china95598.com all rights reserved   闽ICP备05028030号                       关于我们 - 免责声明